After completing installation, use these instructions to check out the product operation. Location Install the thermostat about 1.5m (5 ft) above the floor in an area with good air circulation at average temperature. Do not install the thermostat where it can be affected by: —.

T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Wallplate Installation The thermostat can be mounted horizontally on the wall or on a 2 in. (50.8 mm x 101.6 mm) wiring box. Position wallplate horizontally on the wall or on a 2 in. OUTDOOR TEMPERATURE SENSOR Mounting Thermostat 1. Engage tabs at the top of the thermostat and wall- 2. Press lower edge of case to close and latch.

Honeywell Chronotherm Iv Plus Manual T8611

(HOT) NOTE: To remove the thermostat from the wall, first pull TRANSFORMER. T8600D key locations and descriptions. Program Hold Temp Fig. Thermostat System and Fan key locations. NOTE: Always press the keys with your fingertip or Temperature Settings Refer to Table 2 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. Table 2 and if no changes are necessary, go to the Installer Self-Test section.

Sep 13, 2012  Honeywell chronotherm iv plus manual Products and names mentioned are the property of their respective owners. PDF Owner Manuals and User Guides are NOT affiliated with the products and/or names mentioned in this site. I am replacing a honeywell chronotherm iv plus with a honeywell rth3100c. The old thermostat has a y1, w1 and w2 wire with the y1 jumpered to the w1. The new thermostat has y, aux and e.

The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, system changeover, and outdoor temperature display.

17 and 18 Extended fan operation in heating Extended fan operation in cooling Not used. 21 thru —1 Table 3. Thermostat Installer Setup Options. Factory Setting Display Description — — Conventional applications where equipment controls fan operation in heat mode. Thermostat Installer Setup Options.

(Continued) Installer Setup Number (Press Time ∆ key to Select change) Outdoor temperature display (select models) Not used. 25 thru 29 Deadband Not used. 31 and 32 Minimum off time for the compressor.

Temperature range stops in heating. Press Run Program. Program Set Day/Time Viewing or Resetting Timer Settings When the thermostat activates a timer, the thermostat M14619 flashes Filter until the timer resets. Reset the timer by pressing the i key until the Set Day/Time M14620 2.

If more than one timer is active, all active timers show sequentially when pressing the i key several times. INSTALLER SYSTEM TEST Use the Installer System Test to check the thermostat operation. Refer to Table 4 for a list of the available system tests. CAUTION Equipment Damage Hazard. The Run Program key does not exit this test.

Physical Chemistry Levine 6Th Edition Solutions Manual. Updated a year ago. About 0 Discussions 0 Change Requests. Subscribe 1 Read. Students can access the solutions manual by visiting: www.pearsonhighered.com/advchemistry and selecting the Levine cover and Resources tab. Levine physical chemistry solutions manual. Student Solutions Manual for Quantum Chemistry, 6th Edition. Ira N Levine. ©2009| Pearson. Student Solutions Manual, 5th Edition.

Press Time ∆ or Time ∇ and then the Run Program key to exit. THERMOSTAT INFORMATION 1. Press the Time ∆ key to access the thermostat information. Press the increase key to display the production date code. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in the Off position—set to the On position.

— check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. Wait a minute after seeing the on indicator and then check the registers. Verify operation of heating or cooling equipment in self-test. Enter Installer Setup number 24 and set to 1. Thermostat must have OT terminals and a C7089B1000 installed. Refer to C7089B1000 Installation Instructions and check wiring between the thermostat and sensor.

Honeywell Chronotherm Iv Plus Reset

Our goal is to provide you with a quick access to the content of the user manual for Honeywell Chronotherm IV T8601D. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Honeywell Chronotherm IV T8601D. For your convenience If looking through the Honeywell Chronotherm IV T8601D user manual directly on this website is not convenient for you, there are two possible solutions:. Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Honeywell Chronotherm IV T8601D on full screen, use the button Fullscreen.

Downloading to your computer - You can also download the user manual Honeywell Chronotherm IV T8601D to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase. Advertisement Print version Many people prefer to read the documents not on the screen, but in the printed version.

The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Honeywell Chronotherm IV T8601D but the selected pages only. Summaries Below you will find previews of the content of the user manuals presented on the following pages to Honeywell Chronotherm IV T8601D.

If you want to quickly view the content of pages found on the following pages of the manual, you can use them. Summary of the content on the page No. 1 T8601D Chronotherm® IV Deluxe Programmable Thermostats INSTALLATION INSTRUCTIONS APPLICATION stage heating and cooling systems.

Refer to Table 1 for a general description of the thermostat. All T8601 The T8601 Chronotherm® IV Deluxe Programmable thermostats require a common wire to supply power. Thermostat provides electronic control of 24 Vac single- Table 1. Description of T8601 Thermostats. T8601 System Changeover System Selection Fan Selection Comments D Heat-Cool Automatic Heat-Off-Cool- Summary of the content on the page No. 2 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS NO YES NO 5 FEET NO 1.5 METERS M10106 Fig. Typical location of thermostat.

Remove the wallplate from the wall and drill two Wallplate Installation 3/16 in. Holes in the wall (if drywall) as marked. For The thermostat can be mounted horizontally on the wall firmer material such as plaster, drill two 7/32 in. Or on a 2 in.

Position wallplate holes. Gently tap anchors (provided) into the drilled horizontally on Summary of the content on the page No. 3 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS FOR WRAPAROUND FOR STRAIGHT INSERTION THERMOSTAT INSERTION STRIP STRIP 5/16 IN. C YG O B W R OT OT 7/16 IN. 3 HEAT COMPRESSOR COOL OUTDOOR M4826 2 CONTACTOR DAMPER RELAY TEMPERATURE SENSOR Fig. Proper wiring technique.

FAN HEAT RELAY DAMPER 2 L1 (HOT) Mounting Thermostat L2 1. Engage tabs at the top of the thermostat and wall- 1 TRANSFORMER plate.

Press lower edge of case to close and latch. 1 POWER SUPPLY Summary of the content on the page No.

4 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS • configure Installer Setup, Using Thermostat Keys • check Self-Test, • display outdoor temperature (select models), The thermostat keys are used to: • set the system operation, • set current day and time, • set the fan operation. • program times and setpoints for heating and cooling, • temporarily override program temperatures, See Fig. 8 for the location of the keys. • display present setting, INCREASE TEMPERATURE SET LEAVE TIMES SET Summary of the content on the page No. 5 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Temperature Settings Wait Set Program Set Day/Time Temporary Setting Refer to Table 2 for the default program. If the daytime Em Heat Recovery AM Off energy savings period is not used, press the period key Cool Hold for (Leave or Return) until the time is blank. The fan setting PM Auto feature is available on select thermostat models.

Honeywell

See Filter Em Ht Aux Ht Days Fan F Owner’s Guide, form number 69-0940, for complete Repl Batt Room Outdo Summary of the content on the page No. 6 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 3. Thermostat Installer Setup Options. Installer Setup Other Choices Number Factory-Setting (Press!

Or ' key to change) (Press Time! Actual Select key to change) Display Description Display Description Setting Not used 1 — — — — — a 2 0 Conventional application 1 Heat pump or electric Fan operation where equipment control heat applications where fan operation in heat mode thermostat controls fan operation in heat mode Not used 3 Summary of the content on the page No. 7 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 3. Thermostat Installer Setup Options. Installer Setup Other Choices Number Factory-Setting (Press! Or ' key to change) (Press Time!

Actual Select key to change) Display Description Display Description Setting Temperature 34 90 Highest heating setpoint 40 to 89 Temperature range (1°F range stops in setting. Increments) of heating heating setpoint settings. Temperature 35 45 Lowest cooling setpoint 46 to 99 Temperature range (1°F Summary of the content on the page No. 8 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS 4. Press Run Program. Setting Current Day and Time 1. Press Set Current Day/Time.

System Heat AM NOTES: On initial power up or after an extended power Time Set Program Run Set Current Wake Leave Return Sleep Run Program Day/Time loss, 1:00 pm flashes on the display until a key Fan Heat/Cool Tue Room Program Hold Temp Day Settings System Fan Wake DST Auto is pressed. Daylight Copy Time M14623 Set Day/Time Viewing or Resetting Timer Settings Summary of the content on the page No. 9 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS INSTALLER SELF-TEST Use the Installer Self-Test to check the thermostat oper- Refer to Table 5 for the directions and results of the ation. Refer to Table 4 for a list of the available self-tests. Specific tests.

NOTE: Press Time ∆ to advance to the next test and Time ∇ to go back to the previous test. Press CAUTION Run Program to exit the self-test. Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer Sys Summary of the content on the page No.

10 T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS THERMOSTAT INFORMATION 1. Press the Time ∆ to access the thermostat 4. Press the increase! Key again to display the information. Software revision number. (Example: 001= Revision number 1).

M14613 M14616 2. Press the increase! Key to display the production date code.

The first two large digits are the month and the third digit is the last digit of the year. Press the increase! Key again to display the (Example: 02 Summary of the content on the page No. 11 TROUBLESHOOTING GUIDE Refer to Table 6 for troubleshooting information.

Honeywell Chronotherm Iv Plus User Manual

Troubleshooting Guide. Symptom Possible Cause Action Display does not Thermostat is not being • Check that C terminal is connected to the system transformer. Powered • Check for 24 Vac between R and C terminals. —If missing 24 Vac: — check if the circuit breaker is tripped—reset the circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is Summary of the content on the page No. Troubleshooting Guide.

Symptom Possible Cause Action Cooling does not No power to the thermostat. • Check that C terminal is connected to the system transformer. • Check for 24 Vac between R and W terminals. —If missing 24 Vac: — check if the circuit breaker is tripped—reset the circuit breaker.

— check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in the Off position—set to the On position. — check wiring between thermosta.